VFD energy savings on pumps and fans: the real numbers
With electricity prices in Pakistan where they are, every factory owner is asking the same question: where can we cut the electricity bill? For pumps and fans, the answer is often a variable frequency drive. This article explains why VFD energy savings can be so large, shows how to estimate them for your own equipment, and covers the cases where a VFD will not help.
The problem: full speed, then throttle
Many pumps and fans run at full speed all the time. When less flow is needed, a valve is partly closed or a damper is turned down. The motor keeps working at almost full power while the valve throws the extra energy away as pressure loss and heat. It is like driving with the accelerator flat and controlling speed with the brake.
The affinity laws, in plain words
For centrifugal pumps and fans, three simple rules describe what happens when you change speed:
- Flow changes in proportion to speed.
- Pressure changes with the square of speed.
- Power changes with the cube of speed.
The cube is what makes the difference. At 80% speed the power needed is 0.8 × 0.8 × 0.8 = 0.51, about half. At 70% speed it is about a third.
| Speed | Flow | Power (ideal) |
|---|---|---|
| 100% | 100% | 100% |
| 90% | 90% | 73% |
| 80% | 80% | 51% |
| 70% | 70% | 34% |
A worked example
Take a cooling-tower fan drawing 30 kW at full speed, running 6,000 hours a year. Measurements show that 80% airflow is enough most of the time.
- Power at 80% speed: 30 × 0.51 ≈ 15.4 kW.
- Add around 3% for drive losses: about 15.9 kW.
- Saving: about 14 kW × 6,000 h ≈ 84,000 kWh a year.
Multiply by your own rate per kWh to get the yearly saving in rupees, then compare it with the cost of the drive and installation. On loads like this the payback is often counted in months, not years.
When a VFD does not save much
- High static head. A pump lifting water to a tall tank must always overcome that height, so the cube law applies only to the part above it.
- Already at full load. If the process truly needs full flow all the time, there is nothing to cut.
- Constant-torque loads. Conveyors and positive-displacement pumps save in proportion to speed, not its cube. A VFD still helps with soft starts and control.
How to check your own plant
You do not need special equipment to find the best candidates. Walk the plant and list every pump and fan above roughly 7.5 kW, then for each one note:
- How flow is controlled today: a throttling valve, a damper, a bypass line, or on/off cycling.
- How many hours a year it runs, and whether demand changes between day and night or summer and winter.
- The actual current drawn (a clamp meter reading is enough to start), compared with the nameplate current.
Loads that run long hours with a partly closed valve or damper are where the savings are. A motor already running near full load with the valve wide open is usually not worth changing for energy alone.
Getting the installation right
Savings disappear quickly if the drive keeps tripping or the motor overheats. Size the drive for local summer temperatures, use shielded motor cable with proper earthing, and set up PID control so the drive holds pressure or temperature automatically. Linking the drive to the PLC also lets you see energy use on a production dashboard.
Want a number for your own plant? Send us the motor kW, running hours and how the flow is controlled today. Ask for a VFD assessment.